Land Based Genset (40 kW)

Specification

ENGINE SPECIFICATION
Engine Model 3M10G40/6
Rated Speed 1800 RPM
No. of Cylinder 3
Bore x Stroke (mm) 105 mm x 120 mm
Compression Ratio 15.5:1

Alternator Brand
Model MPS-40-4 MP-40-4
Excitation Brushless
Winding Day 12 12

Genset Specification
KW KVA
Prime Output 40 50
Standby Output 44 55
Phase 1 Phase 3 Phase
Frequency 60Hz

Features

Control Module Specifications

• Back-lit LCD Display
• 3 Phase generator and 3 phase mains monitoring
• Monitoring speed, frequency, voltage, current, oil
pressure, coolant temperature and fuel level.
• Display warning, shutdown and engine status information
• Hours counter provides accurate information for
monitoring and maintenance.

Prime Rating

These ratings are applicable for supplying continuous electrical power
in lieu of commercially purchased power. There is no limitation to the
annual hours of operation and this model can supply 10% overload
power for 1 hour in 12 hours.

Standby Rating

These ratings are applicable for supplying continuous electrical power
in the event of a utility power failure. no overload is permitted on these
ratings